One-Line Diagrams

02:21 / Posted by tech data /

Electrical Systems
We usually depict the electrical distribution system by a graphic representation called a One-Line Diagram. A one-line can show all or part of a system. It is very versatile and comprehensive because it can depict very simple DC circuits, or a very complicated three-phase system.We use universally accepted Electrical Symbols to represent the different electrical components and their relationship within a circuit or system. To interpret one-lines you first need to be familiar with the electrical symbols. This chart shows the most frequently used symbols.
Common Electrical Symbols (Continued)


Interpreting One-Line Diagrams
Now, that you are familiar with electrical symbols, let's look at how they are used in interpreting one-line diagrams. Below is a simple electrical circuit. You can tell by the symbols that this one-line diagram has three resistors and a battery. The electricity flows from the negative side of the battery through the resistors to the positive side of the battery.

Now, let's go through an industrial one-line diagram. When interpreting a one-line diagram, you should always start at the top where the highest voltage is and work your way down to the lowest voltage. This helps to keep the voltages and their paths straight. To explain this easier, we have divided the one-line into three sections.

Area a
Starting at the top, you will notice that a transformer is feeding power to the whole system. The transformer steps the voltage down from 35kV to 15kV, as indicated by the numbers next to the transformer symbol.


Once the voltage has been stepped down, a removable circuit breaker (A1) is encountered. Do you recognize the removable circuit breaker symbol? You can assume this circuit breaker can handle 15kV because it is attached to the 15kV side of the transformer and nothing different is indicated on the one-line.


Following the removable circuit breaker (A1) from the transformer, it is attached to a heavier, horizontal line. This horizontal line represents an Electrical Bus, which is a means used to get electricity to other areas or circuits.

Area b
You will notice that two more removable circuit breakers (B1 and B2) are attached to the bus and feed other circuits, which are at 15kV because there has been no indication of voltage change in the system.

Attached to the removable circuit breaker (B1), a step-down transformer is used to take the voltage in that area of the system from 15kV down to 5kV. On the 5kV side of this transformer, a disconnect switch is shown. The disconnect is used to connect or isolate the equipment below it from the transformer. The equipment below the disconnect is at 5kV because nothing indicates the contrary.

Do you recognize the equipment attached to the lower side of the disconnect switch as being two medium-voltage motor starters? A number of starters could be connected depending upon the particular system requirements.

Now locate the second removable circuit breaker (B2). This circuit breaker is attached to a fused disconnect switch and it is connected to a step-down transformer. Notice that all the equipment below the transformer is now considered low voltage equipment because the voltage has been stepped down to a level of 600 volts or lower. The last piece of electrical equipment in the middle portion of the diagram is another circuit breaker (B3). This time, however, the circuit breaker is a Fixed Low Voltage Circuit Breaker, as indicated by the symbol. Moving to the bottom area of the one-line, notice that the circuit breaker (B3) in the middle is connected to the bus in the bottom portion.


Area c
To the bottom left and connected to the bus is another fixed circuit breaker. Look carefully at the next grouping of symbols. Do you recognize the automatic transfer switch symbol? Also, notice that a circle symbol which represents an emergency generator is attached to the automatic transfer switch. This area of the one-line tells us that it is important for the equipment connected below the automatic transfer switch to keep running, even if power from the bus is lost. You can tell from the one-line that the automatic transfer switch would connect the emergency generator into the circuit to keep equipment running, if power from the bus were lost.

A low-voltage motor control circuit is attached to the automatic transfer switch through a low-voltage bus. Make sure you recognize these symbols. Although we do not know the exact function of the low voltage motor control in this circuit, it is obvious that it is important to keep the equipment up and running. A written Specification would normally provide the details of the application.

On the right side of the third area there is another fixed circuit breaker connected to the bus. It is attached to a meter center, as indicated by the symbol formed by three circles. This indicates that the electric company is using these meters to keep track of power consumed by the equipment below the meter center.

Below the meter center is a Loadcenter or Panelboard that is feeding a number of smaller circuits. This could represent a loadcenter in a building that feeds power to the lights, air conditioning, heat and any other electrical equipment connected to the building. This over-simplified analysis of a one-line diagram gives you an idea of the kind of story such diagrams tell about electrical system connections and equipment. Just keep in mind that although some one-line diagrams may appear overwhelming by virtue of their size and the wide variety of equipment represented, they can all be analyzed using the same step-by-step method.